Customer Helpline : 1860 2081 007 (10:00AM - 7:00PM) Whatsapp Helpline : 6379 88 1007
There are no products matching the selection.
Smart and cutting edge design
Extensive lineup from 8HP to 48HP in 2HP increment
Connectable indoor unit capacity ratio up to 150%
EER/COP has been significantly improved by unique inverter
technology and refrigerant control technology
The outdoor unit size has been significantly reduced by optimizing of equipment.
This allows for a reduction in the required installation area floor space.
Total pipe length of 1,000m and 150m actual pipe length.
From small to large buildings,any application can be supported.
Diverse building air conditioning control functions can be controlled
easily by central air conditioning control.
V-II systems can be applied to a wide variety of Building applications due to the reduced outdoor unit size and piping length capabilities
World’s top class overall piping length of 1,000m allows for application in a wide variety buildings
From transportation of the product to address setting for commissioning, significant improvements have been made which reduce the cost of installation.
Design of outdoor unit allows for lifting straps to be used
Transport with forklift is possible
Low noise, easy operational settings, and comfortable temperature adjustment allows for V-II systems to be used in building air conditioning applications.
Low noise mode
Two low noise modes can be selected automatically by quiet priority setting and capacity priority setting depending on the usage environment and outside temperature load.
Designed for Quick Service response, Easy maintenance and Troubleshooting
Model | UNITS | AJ*306LALHH |
---|---|---|
Maximum Connectable Indoor Unit*1 | 48 | |
Indoor unit connectable capacity - Cooling | kW | 48.0-143.8 |
Power source | 3-phase 4 wire, 400 V, 50Hz | |
Capacity - Cooling | kW | 95.9 |
Capacity - Heating | kW | 107.5 |
Input power - Cooling | kW | 26.66 |
Input power - Heating | kW | 26.45 |
COP - Heating | W/W | 4.06 |
Air flow rate | m3/h | 13,000 + 11,100 x 2 |
Sound pressure level - Cooling | dB(A) | 63 |
Sound pressure level - Heating | dB(A) | 64 |
Maximum external static pressure | Pa | 80 |
Compressor motor output | kW | 3.9 × 3 + 4.5 × 2 |
Heat exchanger fin | Blue fin | |
Dimensions (H×W×D) | mm | 1,690 x 930 x 2 + 1,240 x 765 |
Weight | kg | 296 + 275 + 220 |
Refrigerant charge | kg | 11.8 × 2 + 11.2 |
Connection pipe diameter - Liquid | mm | 19.05 |
Connection pipe diameter - Gas | mm | 34.92 |
Operation range - Cooling | °CDB | -5 to 46 |
Operation range - Heating | °CDB | -20 to 21 |